What should the exhaust gas purification tower pay attention to when maintaining?

There are two types of Waste Gas Purification Tower, respectively vortex plate spray tower (dust removal desulfurization), packing spray tower (and), and two kinds of tower is suitable for many industries, but also need to take regular check on them.

What should the exhaust gas Purification Tower pay attention to when maintaining?

-


1. Check the dosage of neutralization potion every day, carefully record and make dosage calculation to supplement in time;
2. Check the running condition of the Water Pump every day, and check that the sprinkler spray is normal;
3. Check the running condition of the fan, the temperature of the motor and bearing seat, and the noise and vibration of the fan every day;
4. Check and adjust the belt tension every week, and replace the motor belt every quarter;
5. Replace the special engine oil of bearing pedestal within one month in the initial use of the fan, and replace it regularly every quarter in the future;
6. Inject high-quality grease into the motor every quarter;
7. Replace the circulating fluid monthly or regularly. The circulating fluid should prevent saturation, remove sediment timely and keep the water tank clean.
8. Check whether the packing is dirty, impurities or damaged on a monthly or regular basis.
9. Clean the liquid tank of the medicine cabinet every month or regularly to reduce the obstruction of the hot water pump.

 The Manual Air Valve and air flow control valve, ventilation is civil building industrial building, central air-conditioning terminal indispensable accessories for air conditioning and air purification engineering, generally used in air conditioning, ventilation pipe system, used to adjust the tube of the air flow, can also be used for mixing of fresh air and return air conditioning