When upgrading sewage and wastewater with larger impurities, the outlet pipes of the submersible sewage pump in different sumps should not be merged and discharged. When upgrading the general wastewater, the submersible sewage pumps in different sumps may be merged according to the actual situation Induced fan out. Sewage pump suction pipe and outlet pipe flow rate should not be less than 0.7m / s, and should not be greater than 2.0m / s. Drainage pump should be able to automatically start and stop and on-site manual start and stop. Drainage pumps used in the building have submersible sewage pumps, submersible sewage pumps, vertical sewage pumps and horizontal sewage pumps. Multiple pumps can be alternately operated in parallel, but also can be put into operation in stages. As the general site of the building is smaller, the displacement is not large, the drainage pump can give priority to the submersible sewage pump and submerged sewage pump, which submerged sewage pump is generally used in important places; vertical sewage pump and horizontal sewage medicine pump requirements Set the base isolation, self-irrigation water absorption, and occupy a certain site, it is less used in the building. Grinding Steel Ball,Abrasive Steel Ball,Hot Rolling Steel Ball SHANDONG SHENGYE GRINDING BALL CO., LTD , https://www.sdgrindingball.com
Public buildings should be set for each living drainage catchment unit as a backup pump, usually interoperable spiral feeder operation. Do not allow the pressure drain and the building gravity drainage pipe merged discharge. When the catchment can not set the accident drain, the pump should have uninterrupted power supply; when you can close the drainage pipe, it may not provide uninterrupted power supply, but should set the alarm device. Fire elevator pool drain pump flow rate of not less than 10L / s. Sewage pump lift by lifting height, pipe loss calculation is confirmed, then add a certain free head.
Free head should adopt 0.02 ~ 0.03MPa. Sewage disc tray feeder set submersible sewage pump drainage, water pump should be set to fix the auto-coupling device to facilitate overhaul of the pump. A single pump drainage may occur when the backflow should be set check valve. When the submersible sewage pump to enhance large debris, the submersible sewage pump should be equipped with a comminution device; when upgrading with more fibrous waste water, should adopt a large submersible sewage pump.
Sewage pump discharge flow should be designed to select the second life of the drainage; when the displacement adjustment, according to the life of the largest hour of discharge selected. Basement, equipment room, garage flushing the ground drainage, if there are two or more than two drainage pump equipment pump.
When the submersible sewage pump motor power is greater than or equal to 7.5kW or outlet diameter greater than or equal to DN100, the pump can be fixed auto-belt conveyor device; when the submersible sewage pump motor power is less than 7.5kW or a Promise adjustable feeder outlet pipe Diameter less than DN100, the hose can be set to install mobile. When two or more pumps share one outlet pipe, a valve and a check valve shall be installed on each outlet pipe of the water vibrating sieve pump.
This article Keywords: Submersible pumps