Power-Frequency Partial Discharge Test Equipment/ Lab Equipment

Model NO.: HZJF
Weight: 0-100Kg
Power Source: AC 220V/AC 380V
Rated Capacity: 5-1000kVA
Impedance Voltage: 10%
Output Voltage Waveform: Power Frequency, Sine Wave
Output Voltage: AC 0-1000kv
Surface Temperature: Oil Immersed:<55ºC Gas: <50ºC
Partial Discharge: Under Rated Voltage≤5PC
No-Load Loss: 0.2%-0.35%
Insulation Method: Oil, Gas
Trademark: United
Specification: can be customized
Origin: Hu Bei, China
Power-Frequency Partial Discharge Test Equipment/ Lab Equipment


I. Product Introduction & Features:


It is mainly used for testing frequency voltage insulation level of various insulation materials, insulation structure and electrical products, also as partial discharge frequency testing power supply for testing object such as transformer, mutual inductor and lightning arresters. It widely used in electrical manufacturing, power operation departments, research institutes and universities.HZJF System 10kVA/100kV composition
.

1. Test Control Table/Case 
2. Free Gas type transformer
3. Coupling capacitor   
4. Protective resistor           
5. Isolation filter             
6. Partial discharge detector
7. Other accessories         



Hezhong control Unit and PD-free testing transformer are controlling and voltage boosting for test object which boosted to the rated voltage.
Partial discharge detector is detecting and displaying partial discharge capacity.
Isolation filter is device of anti-interference caused by power supply. 
Coupling Capacitor is transmitting partial discharge signal to partial discharge detector.


320*240 LCD screen,high speed thermal printer.
HV voltage,HV current,LV voltage,LV current measuring mode,High-precision sensor and high performance 14digit AD acquisition chip.
Real-time show HV voltage,HV current,LV voltage,LV current,time and withstand result.
Zero-returning detection.When it it back to zero,the test can be started.
Insulation resistance detection function,show insulation strength of test object directly.
Advanced PD-free epoxy insulating sleeve, small partial discharge capacity.
Low impedance voltage.

Automatic control technology, good anti-interference performance.
Rapid electronic protection, high reliability.



II. Main Parameter:
 
Rated Capacity 5-1000kVA Impedance Voltage 10%
Input Voltage AC 220V/AC 380V Output Voltage Waveform Power frequency, sine wave
Output Voltage AC 0-1000kV Surface Temperature Oil immersed:<55ºC
Gas: <50ºC
Partial Discharge Under rated voltage≤5PC No-load Loss 0.2%-0.35%
Insulation Mode Oil, Gas Allowed Continuous Operation Time 1hour as per

III. Company Information:

Wuhan Hezhong Electrical Equipment Manufacture Co., Ltd founded in 2002, reorganized by electrical test equipment factory of former Wuhan high voltage research institute, is a high quality equipment supplier of China State Grid. After years of continuous innovation has become as a professional production and sale electric power testing, test equipment of high-tech enterprise integrates the ability to scientific research, development, production and sales, service, with kinds of patents, its core technology is in the same industry leading lever, and cooperates with the research institutes of Tsinghua University, Peking University and Chiao Tung University. Our sales and service are all over the country and exported to America and Europe, southeast Asia markets such as USA, Singapore and other overseas markets.

Power-Frequency Partial Discharge Test Equipment/ Lab Equipment




 

Swing Beam Shear(CNC)

Hydraulic swing beam shearing machine,Hydraulic shear,Shearing machine design,hydraulic shearing machine,Hydraulic bar shear,Shear cutting machine